2010年9月17日 星期五

HT-0906 24-Bit Precision Controller

HT-0906 24-Bit Precision Load Cell Input Card

Features Introduction Specifications

4-channel strain gauge transducer input

_ Excitation voltage:10 Vdc

_ Internal A/D resolution:24 bit

_ Update speed when Auto-zero Disabled

• Up to 30 KSPS (single channel)

• Up to 4 KSPS (multi-channel)

_ Update speed when Auto-zero Enabled

• Up to 800 SPS (single channel or multi-channel)

_ Transducer sensitivity:1.0 mV/V to 4.0 mV/V

_ Number of channels:4

_ Accuracy:1/200,000 of full scale

(with remote sense & auto zero enabled)

_ Onboard 256 samples A/D FIFO

Motion Control

_ Number of axis:3

_ Pulse output options: OUT/DIR、CW/CCW (26LS31、differential line driver、 driving current:up to 20 mA)

_ Maximum output frequency:500 kHz

_ Encoder Input:24-bit up/down counter for incremental encoder feedback

Isolated Digital Input

_ Number of channels:8

_ Maximum input range (non-polarity):0 V to 24 V

_ Input resistance:2.7 KΩ

Isolated Digital Output

_ Number of channels:8

_ Output type:Power MOSFET

_ Sink current:Up to 300 mA/channel

General Purpose Analog Input

_ Resolution:24-bit

_ Programmable gain:1、2、5、10、20、50、100

_ Number of channels:4

_ Sampling rate:30 kS/s (non-multiplexing)

_ Onboard 256 samples A/D FIFO

Analog Output

_ Resolution:16-bit

_ Output range:±10 V

_ Number of channels: 2

_ Update rate:Up to 5 kS/s

_ Onboard 1 K samples D/A FIFO

_ Driving capability:5 mA

_ Application

• Material test system

_ Transducer Inputs for precise measurement of large-scale transducers

• 4-CH strain gauge-based transducer inputs

• Accuracy up to 1/200,000 counts at full-scale

• Sensitivity from 1.0 mV/V to 4.0 mV/V

• 10 VDC excitation voltage

• Internal 24-bit A/D resolution

_ Motion Controller for servo motor and hydraulic system control

• 3-axis motion controller with OUT/DIR and

CW/CCW pulse output options

• 2-CH 16-bit analog outputs

• A-B phase encoder input with 24-bit counter

_ General-Purpose Analog Inputs for accurate

measurements of LVDT and linear wire potentiometer signals

• 4-CH analog input with 24-bit resolution

• Programmable gains of +/-1.25 V, +/-2.5 V,+/-5 V, +/-10 V

• Up to 30 kS/s sampling rate (single channel)

Note : LVDT: Linear Variable Displacement Transducer

Hung Ta Instrument CO., LTD.